+90 530 236 75 12
+90 530 062 31 79
+90 530 062 31 79
+90 530 236 75 12
Ürün
Stranded Copper (Class2)
Max. Operating Temperature
Max. Short Circuit Temperature
Test Voltage (A.C. 2 kV / 2,5 kV)
Installation Temperature (Min. 5ºC)
  • Areas of Use
  • Areas of Use
  • Technical Specifications
  • Certificates

60227 IEC01 (NYA)

PVC insulated, non-sheathed single core cables

It’s used in fixed premises, dry places, pipes on our under the plasters and in premises which are built with insulators.

Nominal cross Overall diameter Net weight Current carrying capacity in Conductor D.C. resistance

(mm2)

(mm)

(kg/km)

Conduit

(A)

Air

(A)

(ohm/km)

H05V–R (300/500 V)
1,5 2,9 20,4 14,5 24 12,1
2,5 3,6 32 19,5 32 7,41
4 4,1 47,3 26 42 4,61
6 4,7 66 34 54 3,08
10 5,9 110 46 73 1,83
16 6,8 165 61 98 1,15
25 8,2 255 80 129 0,727
35 9,3 345 99 158 0,524
50 10,9 472 119 198 0,387
70 12,5 661 151 245 0,268
95 14,6 915 182 292 0,193
120 16,3 1,144 210 344 0,153
150 17,9 1,417 240 391 0,124
185 19,8 1,755 273 448 0,0991
240 22,7 2,300 320 528 0,0754
300 26,3 2,931 - - 0,0601
400 30,7 3,727 - - 0,0470
500 34,1 4,763 - - 0,0366
630 37,6 6,114 - - 0,0283

TS EN 50525-2-31

BS EN 50525-2-31

IEC 60227-3