+90 530 236 75 12
+90 530 062 31 79
+90 530 062 31 79
+90 530 236 75 12
Ürün
Flex Copper (Class 5)
Max. Operating Temperature
Max. Short Circuit Temperature
Low Smoke (EN 61034)
Halogen Free (EN 50525-1)
Test Voltage (A.C. 2 kV / 2,5 kV)
Installation Temperature (Min. -20ºC)
  • Areas of Use
  • Areas of Use
  • Technical Specifications
  • Certificates

XL-LS0H
Halogen free, flame retardant, heat resistant, single core cables

Used in hotels, hospitals, shopping centers, power plants, information technology centers and in places where human groups are carried by railway sistems, valuable equipments are located , subject to fire danger. These cables do not conduct flame during fire, do not create high smoke density, do not create corrosive ambients and therefore provide health and goods protection.

Nominal cross
(mm²)

Outside diameter
(Yaklaşık mm²)

Net weight
(kg/km)

Conductor D.C. resistance
(20°C | ohm/km)
Current carrying capacity in
Conduit (20°C | A) Air (20°C | A)
H05Z-K (300/500 V)
0,5 2,1 8,5 39 - 11
0,75 2,4 11,5 26 - 16
1 2,5 13,8 19,5 11 20
H07Z-K (450/750 V)
1,5 2,9 19,3 13,3 14,5 24
2,5 3,6 30,7 7,98 19,5 32
4 4,1 44,5 4,95 26 42
6 4,7 63,1 3,30 34 54
10 6,1 107 1,91 46 73
16 7,3 162 1,21 61 98
25 9,0 248 0,780 80 129
35 9,9 336 0,554 99 158
50 12,1 485 0,386 119 198
70 13,8 661 0,272 151 245
95 15,6 894 0,206 182 292
120 17,2 1110 0,161 210 344
150 19,4 1383 0,129 240 391
185 22,5 1717 0,106 273 448
240 24,4 2222 0,0801 320 528
300 27,9 2803 0,0641 - 689
400 33,7 3783 0,0486 - 789

TS EN 50525-3-41

BS EN 50525-3-41