Solid / Stranded Copper (Class 1 / Class 2)
Max. Operating Temperature
Max. Short Circuit Temperature
Test Voltage (A.C. 2 kV)
Installation Temperature (Min. 5ºC)
  • Areas of Use
  • Areas of Use
  • Technical Specifications
  • Certificates

BS 6004

PVC insulated, PVC sheathed, flat cables

Used as surface wiring where there is little mechanical damage risk, or in conduit.

Nominal cross
(mm²)

Outside diameter
(Yaklaşık mm²)

Net weight
(kg/km)

Conductor D.C. resistance
(20°C | ohm/km)
Current carrying capacity in
Conduit (20°C (A)
6192Y (300/500 V)
2 x 1 re 4,1  x  6,4 49,5 18,1 13
2 x 1,5 re 4,7  x  7,6 70,0 12,1 16
2 x 2,5 re 5,6  x  9,2 105,0 7,41 21
2 x 4 rm 6,1  x  10,2 139,0 4,61 27
2 x 6 rm 6,9  x  1 1 ,6 187,0 3,08 34
2 x 10 rm 8,3  x  14,2 298,0 1,83 45
2 x 16 rm 9,4  x  16,2 425,0 1,15 57
6193Y (300/500 V)
3 x 1 re 4,1  x  8,7 71,0 18,1 13
3 x 1,5 re 4,6  x  10,2 98,0 12,1 16
3 x 2,5 re 5,4  x  12,2 146,0 7,41 21
3 x 4 rm 6,3  x  14,5 210,0 4,61 27
3 x 6 rm 6,9  x  16,3 277,0 3,08 34
3 x 10 rm 8,3  x  20,1 442,0 1,83 45
3 x 16 rm 9,4  x  23,0 633,0 1,15 57
(re: Solid , rm: Rijit)

BS 6004:2012