- Areas of Use
- Areas of Use
- Technical Specifications
- Certificates
LOW SMOKE ZERO HALOGEN (LS0H)
Halogen free, flame retardant, single core cables
Used in hotels, hospitals, shopping centers, power plants, information technology centers and in places where human groups are carried by railway sistems, valuable equipments are located , subject to fire danger. These cables do not conduct flame during fire, do not create high smoke density, do not create corrosive ambients and therefore provide health and goods protection.
| Nominal cross (mm²) |
Outside diameter |
Net weight |
Conductor D.C. resistance (20°C | ohm/km) |
Current carrying capacity in | |
| Conduit (20°C | A) | Air (20°C | A) | ||||
| H05Z1-R (300/500 V) | |||||
| 0,5 | 2,1 | 8,8 | 36 | - | - |
| 0,75 | 2,3 | 11,7 | 24,5 | - | 16 |
| 1 | 2,5 | 14,6 | 18,1 | 11 | 19 |
| H07Z1-R (450/750 V) | |||||
| 1,5 | 2,9 | 20,6 | 12,1 | 14,5 | 24 |
| 2,5 | 3,6 | 32,3 | 7,41 | 19,5 | 32 |
| 4 | 4,1 | 47,7 | 4,61 | 26 | 42 |
| 6 | 4,7 | 66,5 | 3,08 | 34 | 54 |
| 10 | 5,9 | 110,5 | 1,83 | 46 | 73 |
| 16 | 6,8 | 165,0 | 1,15 | 61 | 98 |
| 25 | 8,2 | 256,0 | 0,727 | 80 | 129 |
| 35 | 9,3 | 346,0 | 0,524 | 99 | 158 |
| 50 | 10,9 | 474,0 | 0,387 | 119 | 198 |
| 70 | 12,5 | 664,0 | 268 | 151 | 245 |
| 95 | 14,6 | 919,0 | 0,193 | 182 | 292 |
| 120 | 16,3 | 1.148,0 | 0,153 | 210 | 344 |
| 150 | 17,9 | 1.421,0 | 0,124 | 240 | 391 |
| 185 | 19,8 | 1.760,0 | 0,0991 | 273 | 448 |
| 240 | 22,7 | 2.308,0 | 0,0754 | 320 | 528 |
TS EN 50525-3-41
BS EN 50525-3-41