Maximum Operating Temperature

Short Circuit Temperature

Test Voltage (A.C.)

3,5 kV

Installation Temperature Min 5°C

Code BS5467 (SECTORS)
Standarts BS 5467 (694-X)
General Definition XLPE INSULATED, ROUND STEEL WIRE ARMOURED, LOW VOLTAGE ENERGY CABLES (SECTORS)
Application These cables are very durable against mechanical external effects thanks to the armor made of galvanized round steel wires on them. It is suitable for heavy construction, installation and installation conditions. They are used under sweet and salty water under soil and specially produced.
Nominal Cross
Outside Diameter
(approximate)
Net Weight
Current Carrying Capacity
Conductor D.C. Resistance (20°C)
(mm2)
(mm)
(kg/km)
ground
(A)
air
(A)
(ohm/km)
2x50mm2 BS 5467
25,4
1.682
160
220
0,387
2x70mm2 BS 5467
28,8
2.190
200
290
0,268
2x95mm2 BS 5467
32,5
2.976
240
350
0,193
2x120mm2 BS 5467
35,9
3.584
270
410
0,153
2x150mm2 BS 5467
39,3
4.291
310
470
0,124
2x185mm2 BS 5467
44,7
5.542
340
540
0,0991
2x240mm2 BS 5467
49,2
6.910
400
640
0,0754
2x300mm2 BS 5467
53,5
8.355
445
730
0.0601
3x50mm2 BS 5467
27,6
2.206
135
200
0,387
3x70mm2 BS 5467
31,3
2.898
167
250
0,268
3x95mm2 BS 5467
35,7
3.976
195
305
0,193
3x120mm2 BS 5467
38,7
4.792
225
355
0,153
3x150mm2 BS 5467
43,9
6.215
250
405
0,124
3x185mm2 BS 5467
47,7
7.453
280
465
0,0991
3x240mm2 BS 5467
52,5
9.344
325
545
0,0754
3x300mm2 BS 5467
57,1
11.420
365
630
0,0601
4x50mm2 BS 5467
31,0
2.773
135
197
0,387
4x70mm2 BS 5467
36,9
3.996
167
250
0,268
4x95mm2 BS 5467
40,5
5.094
195
305
0,193
4x120mm2 BS 5467
47,3
6.634
225
355
0,153
4x150mm2 BS 5467
49,6
7.959
250
405
0,124
4x185mm2 BS 5467
54,0
9.596
280
465
0,0991
4x240mm2 BS 5467
59,9
12.097
325
545
0,0754
4x300mm2 BS 5467
64,7
14.844
365
630
0,0601
BACK