Maximum Operating Temperature

Short Circuit Temperature

Test Voltage (A.C.)

2,5 kV

Installation Temperature Min 5°C

Code H07V–K (NYAF)
Standarts TS EN 50525-2-31 (IEC 60227-3)
General Definition PVC INSULATED, SINGLE CORE CABLES WITH FLEXIBLE COPPER CONDUCTOR
Application It’s used in fixed premises, dry places, pipes on or under the plasters and in premises which are built with insulators.
Nominal Cross
Outside Diameter
(approximate)
Net Weight
Current Carrying Capacity in
Conductor D.C. Resistance (20°C)
(mm2)
(mm)
(kg/km)
conduit 20°C
(A)
air 30°C
(A)
(ohm/km)
H07V–K (FLEX) 450/750 V
1,5 2,90 19,3 14,5 24 13,3
2,5 3,60 30,7 19,5 32 7,98
4 4,10 44,5 26 42 4,95
6 4,70 63,1 34 54 3,30
10 6,10 107 46 73 1,91
16 7,30 162 61 98 1,21
25 9,00 248 80 129 0,78
35 9,90 336 99 158 0,554
50 12,10 485 119 198 0,386
70 13,80 661 151 245 0,272
95 15,60 894 182 292 0,206
120 17,20 1110 210 344 0,161
150 19,40 1383 240 391 0,129
185 22,50 1717 273 448 0,106
240 24,40 2222 320 528 0,0801
300 27,90 2803 689 0,0641
400 33,70 3783 789 0,0486