70-icon2

Maximum Operating Temperature

160-icon2

Short Circuit Temperature

gerilim-icon

Test Voltage (A.C.)

2 kV

serim-icon

Installation Temperature Min 5°C

Code H05VV–F (300/500 V)
Standarts TS EN 50525-2-11 (IEC 60227.5)
General Definition PVC INSULATED, MULTI-CORE CABLES WITH FLEXIBLE CONDUCTOR
Application It can be used in premises (which have medium mechanical forcing), dry places portable tools, humid places, at home and kitchen tolls. It can also be used at heatres (but it mustn’t youch the places that are over 80 C degrees).
Nominal Cross
Outside Diameter (approximate)
Net Weight
Current Carrying Capacity
Conductor D.C. Resistance (20°C)
(mm2)
(mm)
(kg/km)
air (A)
(ohm/km)
H05VV–F (TTR) 300/500 V
2×0,75
6,40
59
6
26
2×1
6,60
65,5
10
19,5
2×1,5
7,40
85,1
16
13,3
2×2,5
9,20
133
25
7,98
2×4
10,40
180
32
4,95
3×0,75
6,80
70
6
26
3×1
7,00
79
10
19,5
3×1,5
8,10
108
16
13,3
3×2,5
10,00
167
25
7,98
3×4
11,30
230
32
4,95
4×0,75
7,40
86
6
26
4×1
7,90
101
10
19,5
4×1,5
9,00
136
16
13,3
4×2,5
10,90
206
25
7,98
4×4
12,30
283
32
4,95
5×0,75
8,30
108
6
26
5×1
8,60
122
10
19,5
5×1,5
10,00
169
16
13,3
5×2,5
12,10
256
25
7,98
5×4
13,90
360
32
4,95
BACK